EAF Logarithmic, Trigonometric

and FIFO Instructions

Chapter 15

15-9

Figure 15.8

FIFO Load and FIFO Unload Ladder Diagram

130

EXECUTE AUX

FUNCTION

FUNCTION NUMBER:

DATA ADDR:

RESULT ADDR:

28

030

050

050

060

000

G

040

000

G

041

000

G

042

000

G

043

000

G

00 15

FIFO Load

Conditioning Bit

Current Data

Being Loaded

File Full Bit

030

G

031

032

060

G

040 005

File Address

Result Word Address (Number of Words Currently in File)

Input Word Address

File Length

G ( )

070

00

050

000

G

( )

070

00

044

000

G

( )

070

00

The File

130

EXECUTE AUX

FUNCTION

FUNCTION NUMBER:

DATA ADDR:

RESULT ADDR:

29

033

050

050

061

000

G

01 14

FIFO Unload

Conditioning Bit

Current Data

Being Unloaded

Output Word Address

FIle Enpty Bit

033

G

034

035

061

G

040 005

G

File Length

( )

070

00

Output Word Address

File Address

Input Word Address

Important: Read chapter 19 and become familiar with the concepts
introduced in this chapter before attempting FIFO instructions.

Figure 15.9 shows data (111) in the Input Word 060 ready to be loaded into
the File. Toggle the precondition bit 13000 from false to true (0 to 1).
Each time data is entered into the file, it is placed in the highest available
address in the file. Observe that transferring data from the Input Word to
the File does not destroy the data in the Input Word. Also, the Result Word
(050) increments by 1 each time a transfer is performed. The Result Word
indicates the number of words in your file at any given time. You can
monitor the Result Word for this information.