Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 47

Advertising
background image

Installing Your

Programmable Controller

Chapter 4

4-8

Figure 4.2

Ungrounded ac PowerĆDistribution System with Master Control Relay

L1

L2

L3

1FU

2FU

3FU

H

FUSE

L1

L2

L3

H

+

10301

L

N

1

1

4

H

3

H

2

X

1

X

2

1

2

3

4

FUSE

1

2

3

4

1LT

2LT

To minimize EMI generation, you should connect a suppression network: for 120V ac, use AllenĆBradley

cat. no. 700ĆN24; for 220/240V ac, use cat. no. 599ĆKA04.
To minimize EMI generation, you should connect a suppression network: for 120V ac, use AllenĆBradley

cat. no. 700ĆN24; for 220/240V ac, use cat. no. 599ĆKA04.
For a power supply with a groundable chassis, this represents connection to the chassis only. For a power

supply without a groundable chassis, this represents connection to both the chassis and the GND terminal.
In many applications, a second transformer provides power to the input circuits and power supplies for

isolation from the output circuits.

output module

wiring arm

input module

wiring arm

input device

output device

use any number of

EĆstop switches in series

CRM

I/O chassis

power supply

start

to motor starters

enclosure wall

grounding electrode

conductor to groundi

electrode system

grounding

electrode

conductors

connect when applicable

backpanel

ground bus

stepĆdown

transformer

CRM

CRM

CRM

CRM

GND

incoming ac

disc

user dc

supply

to dc I/O devices