Scan Theory

Chapter 8

8-4

Add the execution values for each instruction by using Table 8.A. The

sum of these values added to the I/O scan time is the average scan time.

Table 8.A

These Are the Approximate Execution Time Per Scan (in average

microseconds) and Words Per Scan for Each Instruction

Instruction

Instruction Name

Symbol

True

average

µ

sec.

False average

µ

sec.

Words Per

Instruction

These instructions are features of the MiniĆPLCĆ2/02, MiniĆPLCĆ2/16, and MiniĆPLCĆ2/17

Examine On

Examine Off

Output Energize

Output Latch

Output Unlatch

-[ ]-

-[ / ]-

-( )-

-(L)-

-(U)-

7

5

8

7

7

10
10
10
10
10

6

5

8

6

6

10
10
10
10
10

1

1

1

1

1

1
1
1
1
1

Get

Put

Equal

Less Than

Get Byte

Limit Test

-[G]-

-(PUT)-

-(=)-

-(<)-

-]B[-

-]L[-

15

12

12

14

11

13

10
10
10
10
10
10

-

7

13

13

-

14

10
10

10

1

1

1

1

1

1

1
1
1
1
1
1

Counter Reset

Retentive Timer Reset

Timer OnĆDelay

Retentive Timer OnĆDelay

Timer OffĆDelay

Up Counter

Down Counter

-(CTR)-

-(RTR)-

-(TON)-

-(RTO)-

-(CTD)-

-(CTU)-

-(CTD)-

19

19

51

52

55

38

36

6

6

36

33

39

30

31

1

1

1

1

1

1

1

add 1 word per instruction when its address is 400

8

or greater

add 2 words per instruction when its address is 400

8

or greater

1 word

999 words

1 bit

999 bits

with 2 data values

with 10 data values

with 50 data values

add 8

µ

s per instruction when its address is 400

8

or greater

add 16

µ

s per instruction when its address is 400

8

or greater

1
2
3
4
5
6
7
8
9

10
11