Installing Your

Programmable Controller

Chapter 4

4-15

Figure 4.6

Assembly Diagram of Studs, Bus, and Backpanel to Your Enclosure

12305ĆI

12666

star washer

ground bus or

mounting bracket

scrape paint and

use a star washer

bolt

tapped hole

backpanel

flat washer

ground lug

scrape paint

backpanel

welded stud

flat washer

ground lug

star washer

ground bus or

mounting bracket

scrape paint and

use a star washer

back wall of

enclosure

use a wire brush to remove

paint from threads to allow

ground connection

welded stud

Bolt Mounting of a Ground Bus

or a Chassis to the Backpanel

Stud Mounting of this Backpanel

to the Back Wall of the Enclosure

Stud Mounting of a Ground Bus

or Chassis to the Backpanel

Use 6.35 mm (0.25 in.) bolts to mount the I/O chassis on the enclosure
backpanel. For component spacing and dimensions see Figure 4.7