7-2 Troubleshoot the FLEX Ex Analog I/O Modules

1797-OE8H Module

The 1797-OE8H module has one power that is on when power is applied to
the module and one status indicator for each input.

Table 7.1 1797-IE8H Status Indicators

Indicator

Color

State

Meaning

Status

Red

On

At cycle power – Channel 0 indicator lights when you
cycle power until all internal diagnostics are checked.
After successful power cycle, the indicator goes off if no
fault is present.

After successful powerup – Indicates a critical fault (for
example, diagnostic failure)

Blinking (when
faults are
enabled, and bit
set)

Indicates a noncritical channel fault

Yellow

On/blinking

HART device was found on the associated channel (when
configured)

Power

Off

Module not powered

Green

On

Module receiving power

Blinking

No flexbus communication

1797- OE8

Allen-Bradley

B

-

A

OUT 1

OUT 0

OUT 2

PWR

OUT 7

OUT 6

OUT 5

OUT 4

OUT 3

4

8 CHANNEL ANALOG OUTPUT

41442

A

B

C

A = Status indicators
B = Insertable labels for writing individual input
designations
C = Power indicator