2-10 Understand Configurable FLEX Ex Analog Module Features

If data is sent to the module which is out of range, the value will be clipped and
Diagnostic Data will be set to 11 data out of range.

0

4

8

12

16

20

24

-4.000

0.000

4.000

8.000

12.000

16.000

20.000

Output mA

datatable

Diagnostic Data error

11=data out of range

Diagnostic Data error

11=data out of range

Table 2.4 1797-OE8H Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Analog Fault
State

0

mA as
0…20 mA

0.1% of
0…20 mA

0…22 mA

0…22000
(0…22.000 mA)

1000

Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA

1

% as
0…20 mA

0.2% of
0…20 mA

0…22 mA

0…11000
(0…110.00%)

500

Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA

2

Not assigned

3

Unsigned
integer as
0…20 mA

0.03% of
0…20 mA

0…20 mA

0…65535
(0…22 mA)

3276

Min=0 mA
Max=20 mA
Hold
last=hold
50%=10 mA

4

mA as
4…20 mA

0.1% of
4…20 mA

2…22 mA

2000…22000
(2.000…22.000
mA)

1000

Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA

5

Not assigned

6

7

Unsigned
integer as
4…20 mA

0.03% of
4…20 mA

4…20 mA

0…65535
(4…20 mA)

4095

Min=4 mA
Max=20 mA
Hold
last=hold
50%=12 mA

Output =

datatable

(

1000

)

Output = 20

datatable

(

10000

)

Output = 20

datatable

(

65535

)

Output =

datatable

(

1000

)

Output = 16

datatable

(

65535

)

+ 4