3-14 How to Install Your FLEX Ex Analog Modules

Ground the Module

All I/O wiring must use shielded wire. Shields must be terminated external to
the module, such as bus bars and shield-terminating feed throughs.

Table 3.3 Wiring connections for the 1797-OE8H Module

Output

Output + Output –

Output

Output + Output –

Output 0

A-0

A-1

Output 4

B-17

B-18

Output 1

A-4

A-5

Output 5

B-21

B-22

Output 2

A-8

A-9

Output 6

B-25

B-26

Output 3

A-12

A-13

Output 7

B-29

B-30

+V

Terminals 34 and 50

-V

Terminals 35 and 51

Terminals 16, 33, 40, 41, 42, 43, 44 and 45 are connected to chassis ground.

ATTENTION

Do not use the unused terminals on the terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of your
system.