Command 149, Command 152 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 145

Advertising
background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-21

Command 149

Command 149 is the Write SCAN Status command.

Command 152

The Read Loop Search Type command determines the polling address used to
search for a device that has not responded after multiple requests
(disappeared). Also see Command 129. The HART I/O module has a fixed
setting where 1 = single transmitter, unknown (single unknown) short
addresses of 0 to 15. There are no request data bytes.

Table B.23 Command 149 Request and Response Data Bytes

Byte

Description

Value

Request Data Bytes

0

SCAN_EN

General scan enable/disable

0 = All scanning
disabled
1 = Normal scan
enabled
2 = Special scan
enabled

Response Data Bytes

0

SCAN_EN

Scan enable/disable

0 = All scanning
disabled
1 = Normal scan
enabled
2 = Special scan
enabled

Command-specific Response Codes

2

Error

Invalid selection

5

Error

Too few data bytes received

16

Error

Access restricted

32

Error Busy

Table B.24 Command 152 Response Data Bytes

Byte

Description

Value

Response Data Bytes

0

LOC_MET

Locate method

0 = Single analog

Command-specific Response Codes

16

Error

Access restricted

32

Error Busy

Advertising
This manual is related to the following products: