Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 129

Advertising
background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-5

Response Data Bytes

0

CH_NUM

HART channel number

0…7

1

CH_STATUS

Channel status
bit 7 HARD FAULT
bit 6 REBUILDING
bit 5…0 Reserved

0 = No, 1 = yes
0 = No, 1 = yes

2

(1)

COUNT_0

Byte before next item

3

SHORT_ADDR_0

Instrument 0 short address

4…8

EXT_ADDR_0

Instrument 0 extended address

9

INST_SCAN_0

Instrument 0 scan status
bit 7 SCAN_ENABLE
bit 6 SEARCHING
bits 5…0 Reserved

0 = No, 1 = yes
0 = No, 1 = yes

10

INST_FAULT_0

Instrument 0 scan faults
bits 7…6 Reserved
bit 5 DISAPPEARED
bit 4 APPEARED
bit 3 MISMATCHED
bits 2…0 Reserved

0 = No, 1 = yes
0 = No, 1 = yes
0 = No, 1 = yes

COUNT_I

Byte before next item

SHORT_ADDR_I

Instrument I short address

EXT_ADDR_I

Instrument I extended address

INST_SCAN_I

Instrument I scan status
bit 7 SCAN_ENABLE
bit 6 SEARCHING
bits 5…0 Reserved

0 = No, 1 = yes
0 = No, 1 = yes

INST_FAULT_I

Instrument I scan faults
bits 7…6 Reserved
bit 5 DISAPPEARED
bit 4 APPEARED
bit 3 MISMATCHED
bits 2…0 Reserved

0 = No, 1 = yes
0 = No, 1 = yes
0 = No, 1 = yes

Command-specific Response Codes

2

Error

Invalid selection

5

Error

Too few data bytes received

16

Error

Access restricted

(1)

Data from byte 2 is present in the reply only if one instrument has been found on the requested channel.

Table B.4 Command 129 Request and Response Data Bytes

Byte

Description

Value