Command 154 is the Rebuild Up to 8 Specified Loops command.
Table B.25 Command 154 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0
CH_NUM_0
Channel number 0
—
1
COUNT_0
Number of bytes before next item
…
CH_NUM_i
Channel number i
…
COUNT_i
Number of bytes before next item
Response Data Bytes
0
CH_NUM_0
Channel number 0
—
1
COUNT_0
Number of bytes before next item
2
ERROR_0
Error 0
0 = Channel
number invalid
64 = Invalid
channel number
…
CH_NUM_i
Channel number i
—
…
COUNT_i
Number of bytes before next item
…
ERROR_i
Error i
…
…
…
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
17
Error
Too many items requested
32
Error Busy