B-2 FLEX Ex HART Module Commands

Universal Commands

Table B.1 Universal HART Module Commands

Command

Action

Meaning

0

Read

Read unique device
identification

12-byte device identifiers are
given in the response.

1

Read HART variables (process
values)

Commands are only supported for
compatibility purposes and are
without any meaning.

The transmitters, that is, the
SCAN function, have the following
functions.

• Read primary variable
• Read primary variable as

current (in mA) and percent
range)

• Primary variable is read as

a current (in mA) and four
predefined dynamic
variables

2

3

11

Read unique identifier
associated with tag

The response is a 12-byte device
identifier if the given tag matches
the tag of the multiplexer.

12

Read message

Read the 32-bit message
(also see 17).

13

Selection switch markings in
hand, read description, and date

Read the 8-digit selection switch
marking (tag) and the 16-digit time
and date.

17

Write

Write message

The 32-digit message is written
(also see 12).

18

Write tag, description, and date

Save an 8-digit (tag), a 16-digit
description, and date.