Table 2 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 118

Advertising
background image

Publication 1797-6.5.3 - March 2006

A-6 Specifications

Table 2

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1 A, 20

µJ, or 25 mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

This module, 1797-IE8H, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36 to 39, and 46 to 49 shall not be

connected.

WARNING: Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(

µH)

Male Bus

Connector

5.8

400

A-G

3.0

3.0

Advertising
This manual is related to the following products: