Wire the terminal base units, Wire the terminal base units -10 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 62

Advertising
background image

Publication 1797-6.5.3 - March 2006

3-10 How to Install Your FLEX Ex Analog Modules

3. Make sure the pins on the bottom of the module are straight so they will

align properly with the connector in the terminal base unit.

4. Position the module (4) with its alignment bar (5) aligned with the

groove (6) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit.

The module is seated when the latching mechanism (7) is locked into
the module.

6. Make certain that you only connect terminal base units to other

intrinsically safe system modules or adapters to maintain the integrity of
the intrinsically-safe backplane.

7. Remove cap plug (8) and attach another intrinsically safe terminal base

unit to the right of this terminal base unit if required.

Make sure the last terminal base has the cap plug (8) in place.

The adapter is capable of addressing eight modules. Do not exceed a maximum of
eight terminal base units in your system.

Wire the Terminal Base
Units

Wiring the FLEX Ex I/O analog modules is done through the 1797-TB3 and
1797-TB3S terminal base units.

41307

ATTENTION

The FLEX Ex analog I/O modules do not receive primary
operational power from the backplane. +/-V dc power must be
applied to your module before operation. If power is not
applied, the module position will appear to the adapter as an
empty slot in your chassis. If the adapter does not recognize
your module after installation is completed, cycle power to the
adapter.

Make certain that you power these modules with an
intrinsically safe power supply. Do not exceed the values listed
in the specifications for the modules.