Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 74

Advertising
background image

Publication 1797-6.5.3 - March 2006

4-6 Input, Output and Configuration Files for the Analog I/O Modules on the ControlNet Network

The following FLEX Ex adapter status word for a PLC-5 controller results.

As an example, in a PLC-5 system, the adapter status word bit descriptions are
shown in the following table.

41629

Bit:

15

9

10…15

8

7

6

5

4

3

2

1

0

I/O Module Fault Bits

I/O Status Bit

Node Address Changed Bit

Created by PLC-5 controller

Table 4.1 Adapter Status Word Bit Descriptions

Bit Description

Bit

Explanation

I/O Module Fault

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed
(Created by PLC-5
controller.)

8

This bit is set (1) when the node address switch setting has
been changed since power-up.

I/O State (Created by
PLC-5 controller.)

9

Bit = 0 - idle
Bit = 1 - run

10…15

Not used – set to 0