Command 134 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 133

Advertising
background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-9

Command 134

The Read Scan List command returns the extended addresses of the
transmitters. No more than 49 instruments will be returned. If the index is too
large, no list is generated and only the index is present in the reply.

7…11

EXT_ADDR_I

Extended address of instrument I

12

COUNT_I

Bytes before next item

13

ERROR_I

Error I

Table B.9 Command 134 Request and Response Bytes

Byte

Description

Value

Request Data Bytes

0…1

INDEX

Instrument scan list index

Response Data Bytes

0

INDEX

Instrument scan list index

2…6

EXT_ADDR_0

Extended address of first instrument

7…11

EXT_ADDR_I

Extended address of instrument I

Command-specific Response Codes

5

Error

Too few data bytes received

16

Error

Access restricted

32

Error

Busy

Table B.8 Command 133 Request and Response Data Bytes

Byte

Description

Value

Advertising
This manual is related to the following products: