Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 46

Advertising
background image

Publication 1797-6.5.3 - March 2006

2-16 Understand Configurable FLEX Ex Analog Module Features

Analog Output Module (1797-OE8H) Image Table Mapping

Table 2.13 Input Map (Read Words)

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

0

Flt

Alm

ch7

Flt

Alm

ch6

Flt

Alm

ch5

Flt

Alm

ch4

Flt

Alm

ch3

Flt

Alm

ch2

Flt

Alm

ch1

Flt

Alm

ch0

Reserved

Diagnostic Status

1

Reserved

2

H

Rb

ch 7

H

Rb

ch 6

H

Rb

ch 5

H

Rb

ch 4

H

Rb

ch 3

H

Rb

ch 2

H

Rb

ch 1

H

Rb

ch 0

H

Fail

ch 7

H

Fail

ch 6

H

Fail

ch 5

H

Fail

ch 4

H

Fail

ch 3

H

Fail

ch 2

H

Fail

ch 1

H

Fail

ch 0

3

H

Tmt

ch 7

H

Tmt

ch 6

H

Tmt

ch 5

H

Tmt

ch 4

H

Tmt

ch 3

H

Tmt

ch 2

H

Tmt

ch 1

H

Tmt

ch 0

H

Cm

ch 7

H

Cm

ch 6

H

Cm

ch 5

H

Cm

ch 4

H

Cm

ch 3

H

Cm

ch 2

H

Cm

ch 1

H

Cm

ch 0

Where: ch = channel

Flt Alm = Fault Alarm
H Rbd = HART Rebuild
H RB = HART Readback
H Fail = HART Failure
H Tmt = HART Transmitter
H Cm = HART Communication

Table 2.14 Output Map (Write Words)

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

0

Rese

rved

Glbl

Rst

Reserved

Dig
Out

ch 7

Dig
Out

ch 6

Dig
Out

ch 5

Dig
Out

ch 4

Dig
Out

ch 3

Dig
Out

ch 2

Dig
Out

ch 1

Dig
Out

ch 0

1

Channel 0 Output Data

2

Channel 1 Output Data

3

Channel 2 Output Data

4

Channel 3 Output Data

5

Channel 4 Output Data

6

Channel 5 Output Data

7

Channel 6 Output Data

8

Channel 7 Output Data

Where: ch = channel

Dig Out = Digital Output
Glbl Rst = Global Reset

Advertising