Publication 1797-6.5.3 - March 2006

About the FLEX Ex HART Analog Modules 1-13

When these tags are initialized, a JSR to the HART_initialize routine is
performed.

Modify Your Ladder-Logic Routine

With this background information, it is now time to modify the routine to
meet the needs of your application. To do so, perform the following steps:

1. Make sure your wiring is correct and make note of your node address,

the slot location of the FLEX Ex HART I/O module and the channel
with your field device.

2. Load the program into Logix5000 software.

3. Modify the members of the HART_initialize tag to match your setup.

4. Modify the members of the HART_Target tag to match your setup.

5. If you plan to use a HART write command, which requires data to be

sent to the field device, modify the associated CMDx_cmd tag with the
associated data.

6. Download the program to the ControlLogix controller.

Table 1.3 HART_Init_Status Tags

Tag Name

Description

Data Type

HART_Init_Status.Started

Indicates when the command is in
process

BOOL

HART_Init_Status.Done

Indicates when the command has
completed without error

HART_Init_Status.Error

Indicates when the command has
completed with error

HART_Init_Status.Error_Code

If the CMDx_Status.Error bit is set,
the associated error code is placed
here

INT

HART_Init_Status.HART_Channels_
Found

If the CMDx_Status.Done bit is set,
the tag containing the list of
channels with active HART field
devices