1797-oe8h calibration item byte channel-mask -19, 1797-oe8h calibration item byte channel-mask – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 95

Advertising
background image

Publication 1797-6.5.3 - March 2006

Calibrate Your Module 5-19

1797-OE8H Calibration Item Byte Channel-Mask

The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, for example, 0x03 >
channel 0 and 1 have to be calibrated. Only one channel can be calibrated at a
time. If there are more channels selected within the calibration commands, the
I/O module signals an error.

Table 5.14 1797-OE8HCalibration Item Byte Value Identifier List

Identifier (Decimal)

Value

Access Rule

0

Offset channel 0

Read/write

7

Offset channel 7

8

Gain channel 0

15

Gain channel 7

16

Offset current-read-back
channel 0

23

Offset current-read-back
channel 7

24

Gain current-read-back
channel 0

31

Gain current-read-back
channel 7

32

Offset voltage-read-back
channel 0

39

Offset voltage-read-back
channel 7

7

6

5

4

3

2

1

0

Calibrate channel 0

:

Calibrate channel 1

Calibrate channel 7