Publication 1797-6.5.3 - March 2006

2-4 Understand Configurable FLEX Ex Analog Module Features

Data Format

You must choose a module data format in your user program. Formats 8, 9, 10
and 15 are not used. If they are selected for a channel quad, a configuration
fault will occur and will be reported as Diagnostic Data 2. All data for that
channel quad will be set to zero (0).

• Formats 5, 12, 13 and 14 are 2’s complement data formats, and will

return data in that form.

• 12 Formats are available

• Default format is 0 to 20 mA

• The data format selected interprets input readings and returns them to

the PLC

controller

Table 2.3 1797-IE8H Data Formats

Data
Format

Format

Resolution Input

Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Error
Steps

0

0…20 mA
as mA

0.1% of
0…20 mA

0…22 mA Datatable = 1000 (input)

0…22000
(0…22.000 mA)

1000

With
error
steps

1

0…20 mA
as %

0.2% of
0…20 mA

0…22 mA

0…11000
(0…110.00%)

500

2

0…20 mA
as

√%

0.19% of
0…20 mA

0…22 mA

0…10488
(0…104.88%)

524

3

0…20 mA
as
unsigned
integer

0.03% of
0…20 mA

0…20 mA

0…65535
(0…22 mA)

3276

4

4…20 mA
as mA

0.1% of
4…20 mA

2…22 mA Datatable = 1000 (input)

2000…22000
(2.000…22.000
mA)

1000

Datatable = 10000

input

(

20

)

Datatable = 10000

input

20

IF…Square_Root_Threshold

input

20

< 10000

Else…datatable = 0

Datatable = 65535

input

(

20

)