Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 91

Advertising
background image

Publication 1797-6.5.3 - March 2006

Calibrate Your Module 5-15

Table 5.10 1797-OE8H Interpretation of Command Data Structure Content During Write Access

Command Byte

Item Byte

Data1 Byte

Data2 Byte

Reserved (Binary)

Command Bits 0…5 (Decimal)

10

(1)

1

Calibration command min scale

Channel-Mask

Reserved

(4)

Reserved

(4)

2

Calibration command max scale

3

Write measured min scale value (Current, uA)

Value
low-byte

Value
high-byte

4

Write measured min scale value (Voltage, uV)

5

Write measured max scale value (Current, uA)

6

Write measured max scale value (Voltage, uV)

7

Reserved

(2)

8

Set all calibration values to default

Reserved

(4)

Reserved

(4)

Reserved

(4)

9

Set one specified calibration value to default

Value identifier (0)

10

Reserved

(3)

Reserved

(3)

Reserved

(3)

Reserved

(3)

11

Reserved

(4)

12

Reserved

(4)

13

Reserved

(4)

14

Save calibration data to EEPROM

Reserved

(4)

Reserved

(4)

Reserved

(4)

15…63 Reserved

(2)

(1)

Always must be 10

bin

.

(2)

Do not use. Designated for future use.

(3)

Reserved. Used during manufacture of the product. Do not use.

(4)

In attempt to write this byte, write 0.

Advertising
This manual is related to the following products: