Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-3

Common Practice
Commands

Device-specific Commands

The following commands provide device-specific information on the HART
I/O modules.

Command 128

Command 128 is Read Parameter Assignment of the Multiplexer. There are no
request data bytes.

Table B.2 Common Practice HART Module Commands

Command

Action

Meaning

38

Write

Reset configuration changed
flag

Delete status information.

41

Perform device self-test

Performs the device self-test
similar to turning on the power
supply.

If no error occurs, the malfunction
status message is deleted (if it had
been set).

42

Perform device reset

Immediately after the command is
confirmed, a reset of the device
HART controller is performed.

48

Read

Read additional device status

Table B.3 Command 128 Response Data Bytes

Byte

Description

Value

Response Data Bytes

0

MAX_DR_PM

Max delayed response for primary master

1

1

MAX_DR_SM

Max delayed response for secondary
master

0

2

NUM_DR_PM

Delayed response in use for primary
master

3

NUM_DR_SM

Delayed response in use for secondary
master

4

CH_SIGN

Physical signalling on HART channels

0 = BELL 202

5

MAX_CH

Max number of HART channels

8

6…7

MAX_INST

Max number of HART instruments

8

8…9

NUM_INST

Number of HART instruments in the list

10…11 NUM_SCAN

Number of HART instruments scanned

12

MODE

Master bit and timing

1 = Primary