Publication 1797-6.5.3 - March 2006

Calibrate Your Module 5-11

1797-IE8H Calibration with Offset and Gain

You must calibrate the offset from a channel before gain is calibrated at the
same channel, because the gain value depends on the offset value. During the
calibration of offset, the corresponding gain value is declared invalid. Before
all values are calibrated, there is a calibration error displayed within the Real
Time Data in the diagnostic status. After calibration is complete, the calibrated
values are stored in the RAM area by the I/O module. Therefore, a store
command is necessary to cause the I/O module to transfer the RAM content
to the EEPROM.

Use the following guidelines when setting the offset and gain calibrations:

• To calibrate a channel according to offset, the corresponding channel

must be sorted, or opened, so that flow is 0.00 mA.

• To calibrate a channel according to gain, the corresponding channel

must be supplied with 20.00 mA.

• Set the I/O module ambient temperature in the range of 25…±5 °C.
• Check the calibration status to see if it is idle or erroneous before

sending the calibration command by reading attribute 67

hex

.

Calibration Command
Given Back by the I/O Module

Indicates

Idle or erroneous

Calibration is complete

Pending

Poll the status again and recheck

Does not correspond with the first written
command

Access conflict with another calibration
device or another access error — repeat
the calibration command

Idle and it corresponds with the first written
command

Successful calibration by the module