FLEX Ex HART Module Commands B-7
Command 131
For the given long frame addresses, the Read Static Data of Transmitters
command returns the following transmitter data:
• Current loop number, 0 to 15
• Polling address
• Supported HART revision
• Minimum count of required preambles, 5 to 20
There are no request data bytes.
Table B.6 Command 131 Response Data Bytes
Byte
Description
Value
Response Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
ERROR_0
Error 0
0 = Instrument
present. Data for
that instrument is
included in reply.
64 = Unknown
instrument. Data
for that
instrument is not
included in reply.
…
EXT_ADDR_I
Extended address I
—
…
ERRO_I
Error I
…
…
…
Command-specific Response Codes
16
Error
Access restricted
32
Error
Busy