Hart target tags -9 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 23

Advertising
background image

Publication 1797-6.5.3 - March 2006

About the FLEX Ex HART Analog Modules 1-9

HART Target Tags

The HART_Target tag consists of four members:

• Path — HART_Target.Path

The Path specifies the direction the message follows to get to the
desired target node. The data type is string.

• Slot — HART_Target.Slot

The Slot indicates the specific place where the I/O module is attached
to the FLEX Ex adapter. The data type is SINT.

1 = the closest module to the adapter

8 = the module farthest from the adapter

0 = the adapter

• Channel

The Channel indicates which analog channel, 0 to 7, is desired. The data
type is SINT.

• Host_Group

The FLEX Ex HART modules have two message-access ports into
them allowing two systems to gather information from the module
concurrently. The data type is SINT.

The HART_Groups are numbered either 1 or 2. If there are no other
systems accessing the FLEX Ex Hart I/O module, that is, an asset
management system, then select the first HART_Group by setting this
value to 1.

IMPORTANT

If multiple owners access or control the same FLEX Ex HART I/O
module and field device, they must maintain identical
configurations.