Communication over the flex ex backplane, Communication over the flex ex backplane -3, Scheduled data transfer -3 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 71: Scheduled data transfer

Publication 1797-6.5.3 - March 2006
Input, Output and Configuration Files for the Analog I/O Modules on the ControlNet Network 4-3
Communication Over the
FLEX Ex Backplane
One 1797-ACNR15/B ControlNet Ex adapter can interface up to eight
terminal base units with installed FLEX Ex modules, forming a FLEX Ex
system of up to eight slots.
The adapter communicates to other network system components (typically
one or more controllers or scanners, and/or programming terminals) over the
ControlNet network. The adapter communicates with its I/O modules over
the FLEX Ex backplane.
Configuration data is not continuously updated to the module.
Scheduled Data Transfer
Scheduled data transfer:
• is continuous.
• is asynchronous to the controller program scan.
• occurs at the actual rate displayed in the Actual Packet Interval field on
the programming software ControlNet I/O mapping (monitor) dialog
I/O Module
I/O Module
I/O Module
Configuration
Configuration
Configuration
Inputs
Inputs
Inputs
Status
Outputs
Status
Status
Outputs
Outputs
Read
Words
Write
Words
0
X
Slot 0
Slot 1
Slot 7
Network
ControlNet Ex
Adapter
Read
Write
41626