B-12 FLEX Ex HART Module Commands

Command 137

For the given long frame addresses, the Write SCAN Status of the Transmitters
command sets the SCAN status of the transmitters (0 = disable SCAN, 1 =
enable SCAN). No more than 31 instruments may be requested.

Command-specific Response Codes

5

Error

Too few data bytes received

16

Error

Access restricted

17

Error

Too many items requested

32

Error Busy

Table B.12 Command 137 Request and Response Data Bytes

Byte

Description

Value

Request Data Bytes

0…4

EXT_ADDR_0

Extended address of instrument 0

5

COUNT_0

Bytes before next item

6

SCAN_0

Scan enable/disable on instrument 0

0 = Scan disable
1 = Scan enable

EXT_ADDR_I

Extended address of instrument I

COUNT_I

Bytes before next item

SCAN_I

Scan enable/disable on instrument I

Response Data Bytes

0…4

EXT_ADDR_0

Extended address of instrument 0

5

COUNT_0

Bytes before next item

6

ERROR_0

Error 0

0 = No error.
31 = The scan
value sent is
identical to the
current one.
64 = Unknown
instrument. No
data is included
for that
instrument.
65 = Scan value
not allowed. No
data included for
that instrument.

Table B.11 Command 136 Request and Response Bytes

Byte

Description

Value