About the FLEX Ex HART Analog Modules

What This Chapter Contains

Read this chapter to familiarize yourself with the input and output analog
modules.

What the FLEX Ex Analog
I/O Modules Do

The 1797-IE8H module accepts up to 8 analog inputs. The inputs are
non-isolated and will accept current in either of the following two ranges: 4 to
20 mA or 0 to 20mA. The default input range is 0 to 20 mA. The inputs have
both fixed hardware filters and selectable firmware digital filters.

Similarly, the 1797-OE8H module provides as many as eight analog outputs.
The outputs are nonisolated and will provide current in either of the following
two ranges: 4 to 20 mA or 0 to 20 mA. The default output range is 0 to 20 mA.

Each module offers host of features including:

• Local microprocessor intelligence for advanced features

• Full functionality without switches or jumpers

• Multiple data ranges that can be independently programmed

in channel groups

• Lead breakage detection

• Overrange/underrange alarms

• Remote transmitter alarm

For

See

What the FLEX Ex Analog I/O
Modules Do

1-1

How FLEX Ex Analog Modules
Communicate with Programmable
Controllers

1-2

Physical Features of Your Analog I/O
Module

1-3

Chapter Summary

1-15