Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 167

Advertising
background image

Publication 1797-6.5.3 - March 2006

Configure the 1797-OE8H Module in RSLogix 5000 Software Over the ControlNet Network D-3

Data Format Bits

3

2

1

0

7

6

5

4

Range

Resolution

Full Range

Interpretation

Data Value Table

Count per mA

0

0

0

0

0…20 mA

0.1% of 0…20 mA

0…22 mA

0…22 mA

0…22000

1000

0

0

0

1

0…20 mA

0.2% of 0…20 mA

0…22 mA

0…110%

0…11000

500

0

0

1

0

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

0

0

1

1

0…20 mA

0.3% of 0…20 mA

0…20 mA

Unsigned Integer

0…65535

3276

0

1

0

0

4…20 mA

0.1% of 4…20 mA

2…22 mA

2…22 mA

2000…22000

1000

0

1

0

1

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

0

1

1

0

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

0

1

1

1

4…20 mA

0.3% of 4…20 mA

4…20 mA

Unsigned Integer

0…65535

4095

1

0

0

0

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

1

0

0

1

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

1

0

1

0

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

1

0

1

1

0…20 mA

0.28% of 0…20 mA

0…22 mA

D/A Count

0…8000

363

1

1

0

0

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

1

1

0

1

4…20 mA

0.16% of 4…20 mA

3…21 mA

-6.25…+106.25%

-625…+10625

625

1

1

1

0

4…20 mA

0.16% of 4…20 mA

2…22 mA

-12.5…+112.5%

-1250…+11250

625

1

1

1

1

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid

Not Valid