1797-ie8h calibration item byte channel-mask -8, 1797-ie8h calibration item byte channel-mask – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 84

Advertising
background image

Publication 1797-6.5.3 - March 2006

5-8 Calibrate Your Module

1797-IE8H Calibration Item Byte Channel-Mask

The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, for example, 0x03 >
channel 0 and 1 have to be calibrated.

Table 5.7 1797-IE8H Interpretation of Calibration Data Structure Content During Read Access (Pending Status)

Command Byte

Item Byte

Data1 Byte

Data2 Byte

Status (Binary)

Command Bits 0…5 (Decimal)

10

Pending

1

Calibration of offset at 25 °C is in process
according to channel-mask

Channel-mask

0

0

2

Calibration of gain at 25 °C is in process according
to channel-mask

3…7

The unknown command is trying to be interpreted

x

(2)

x

(2)

x

(2)

8

All calibration values are set to default

0

0

0

9

The specified calibration value is set to default

Value-identifier

10

Reserved

(1)

Reserved

(1)

Reserved

(1)

Reserved

(1)

11

Reserved

(1)

12

Reserved

(1)

13

Reserved

(1)

14

The calibration content is saved to EEPROM

x

(2)

x

(2)

x

(2)

15…61 Unknown command is mirrored back

0

0

0

62

Reserved

Reserved

Reserved

Reserved

63

Reserved

(1)

Reserved. Used during manufacture of the product. Do not use.

(2)

The received values are mirrored back.

7

6

5

4

3

2

1

0

Calibrate channel 0

:

Calibrate channel 1

Calibrate channel 7