Command 158 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 147

Advertising
background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-23

Command 158

The Read Special Loop SCAN Parameters command returns the transmitter
data for the given loop, if available. These include:

• Loop number
• Error flag (0 = ok, 1 = special SCAN not active)
• Polling address (always 0, no multidrop)
• Selected SCAN command
• Long frame address
• Number of available data bytes
• Data bytes themselves (if any)

Table B.26 Command 158 Request and Response Data Bytes

Byte

Description

Value

Request Data Bytes

0

CH_NUM

Channel number

0…7

Response Data Bytes

0

CH_NUM

Channel number

0…7

1

ERROR

Error

0 = Special scan
set up for the
selected channel
1 = Special scan
not set up (reply
is truncated to
2 bytes)

2

SHORT_ADDR

Short address used

3

THRESH

Threshold data length for special scan

0…62

4

SCAN_CMD

Scan command being used

5…9

EXT_ADDR

Extended address of instrument

10

LENGTH

Length of data bytes available

> 0 if data
available

11…

DATA

Special scan data (if any)

Command-specific Response Codes

2

Error

Invalid selection

5

Error

Too few data bytes received

16

Error

Access restricted

32

Error Busy

Advertising