Publication 1797-6.5.3 - March 2006

F-4 FLEX Ex HART Modules Network Messaging

Handle replaces Preamble. Handle is a number you supply so that the module
returns the Handle with the associated response from the HART command.

The response from the HART command is reformatted to add this handle and
to add additional status information.

Figure F.4 Response from the HART Command

The six header bytes are added in the front of the HART message response
while the remaining format is unchanged. These six bytes contain the
following information:

• Response Source

• Next Assembly

Pointer to assembly for next access.

• Channel

Status
(6 Bytes)

Pass
Through
Handle

Start
Character

Address

Command

Byte Count

(Response
Code)

Data

Checksum

Byte

0

1

2

3

4

5

Bit

0…2

3…7

0…7

0…7

0…7

0…3

4

5

6

7

0

1

2…7

Resp

Source

Next assy index

Ch

Handle

Resp
Error

Assy

Access

Error

Chain

Data

Req

allow

Loop

status

avail

Lock

Cold

Start

Res

Value

Meaning

0

Not valid (default)

1

Source is HART response

2

Source is Scan data

3

CMD 48 response

4…7

Reserved