FLEX Ex HART Modules Network Messaging

What This Appendix
Contains

This appendix discusses:

• How to communicate with the FLEX Ex HART modules via the MSG

or CIO instruction

• The differences between Attributes and Assembly Indexes
• Enhancements to the HART frame

Communication

The messaging between the controller and the HART I/O module is handled
via MSG or CIO instructions, depending on the controller type. These ladder
logic instructions need specific details for proper operation. In particular, they
need four items:

• Class

The Class value for FLEX Ex is 7D hex.

• Instance

The Instance is a number between 1 and 8. This number indicates the
module location relative to the adapter module. Use 1 for the module
connected directly to the adapter.

• Service

The Service value is 0E hex for Get Attribute Single and 10 hex for Set
Attribute Single. Use a Service value of 0E hex to read data from the
adapter and 10 hex to write data to the adapter.

• Attribute

The Attribute value is based on the Attribute Values table.