Remote fault alarm -5, Remote fault alarm – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 19

Advertising
background image

Publication 1797-6.5.3 - March 2006

About the FLEX Ex HART Analog Modules 1-5

Remote Fault Alarm

The Remote Fault Alarm is primarily intended for use with remote transmitter
loops.

For example, the remote transmitter may be measuring temperature and
converting it to a standard mA signal. In such a loop, though, the input module
cannot determine the state of the loop on the far side of the transmitter.
However, the remote transmitter may be capable of diagnosing a problem in
the remote loop and signal the input module local loop with a preprogrammed
out of range (high or low) value.

The Remote Fault Alarm allows the 1797-IE8H module to work with
transmitters like the one just described. You must use the Remote Transmitter
Error Up or Down feature, see page 2-3, to configure your application for
Remote Fault notification.

For example, you must determine if you want a remote fault to cause
high out of range values or low out of range values to be returned to
the controller.

Use Remote Fault Alarm to Determine High High or Low Low Alarm Levels

If you do not have a remote transmitter in your loop, this alarm can also be
used to program a high high or low low alarm level between the levels which
actuate the overrange or underrange alarms and the high or low local fault
alarms.

IMPORTANT

Once the alarm is issued, it remains active as long as the input
signal value remains above the programmed value.

IMPORTANT

When establishing high high or low low alarms, you can only
select one side (high or low). You must use the Remote
Transmitter Error Up or Down feature in conjunction with this
alarm.

Advertising
This manual is related to the following products: