About the FLEX Ex HART Analog Modules 1-11

HART Initialize Tags

The HART_Target tag consists of four members:

• Path — HART_Target.Path

The Path specifies the direction the message follows to get to the
desired target node. The data type is string.

• Slot — HART_Target.Slot

The Slot indicates the specific place where the I/O module is attached
to the FLEX Ex adapter. The data type is SINT.

1 = the closest module to the adapter

8 = the module farthest from the adapter

0 = the adapter

• Channel

The Channel indicates which analog channel, 0 to 7, is desired. The data
type is SINT.

Your
Ladder-logic
Program

HART_Target

CMDx_cmd

Status

CMDx_reply

HART_CMD_x

Convert CMD
Data Type to
Generic HART
Frame

Convert Generic
HART Reply
Frame to Specific
Reply Data Type

Generic_HART
Command Frame

Generic_HART
Reply Frame

Status

Send_HART_SF

Send Message
to Target and
Poll for a
Response