5-12 Calibrate Your Module

1797-OE8H Calibration
Features

The following features are unique to the 1797-OE8H module:

• There are six values per channel that the I/O module uses to calculate

the corresponding calibration values (offset and gain).

Min Scale DAC at 1500

dec

about 1 mA

Max Scale DAC at 6700

dec

about 20 mA

Current-read-back Min Scale at 1500

dec

about 1 mA

Current-read-back Max Scale at 6700

dec

about 20 mA

Voltage-read-back Min. Scale at 1500

dec

Voltage-read-back Max Scale at 6700

dec

• The module internally calculated calibration values are:

Offset DAC
Gain DAC
Offset I-read-back
Gain I-read-back
Offset U-read-back
Gain U-read-back

• All calibration values are stored in the module non-volatile EEPROM.
• Only one channel can be calibrated at a time according to one

calibration value (max scale or min scale values).

• The actual date must be transmitted after calibration to the I/O module

and stored in the module non-volatile EEPROM. The data can be read
out over the EDT channel.

• The whole calibration can be set to default values by sending a reset

command. The default date is Jan,01,2000.

• A specified calibration value can be set to default by sending a reset

command for that channel.

• There is a special command to store the whole calibration data from

RAM to EEPROM within the I/O module.

• If one value, except the calibration date, isn’t calibrated yet, or if you set

one value to default, the I/O module displays a calibration error within
the Real Time Data diagnostic field.