Input, Output and Configuration Files for the Analog I/O Modules on the ControlNet Network 4-5

I/O Structure

Output data is received by the adapter in the order of the installed I/O
modules. The output data for slot 0 is received first, followed by the output
data for slot 1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter status word.
This is followed by the input data from each slot, in the order of the installed
I/O modules. The input data from slot 0 is first after the status word, followed
by input data from slot 1, and so on up to slot 7.

Adapter Status Word

The status word consists of:

• I/O module fault bits – 1 status bit for each slot

Additionally, in the case of a PLC-5 controller, it adds:

• Node address changed – 1 bit (created by PLC-5 controller)

• I/O status – 1 bit (created by PLC-5 controller)

ControlNet Adapter

Read Data

Adapter Status

Slot 0 Input Data

Slot 1 Input Data

Slot 7 Input Data

Slot 0 Output Data

Slot 1 Output Data

Slot 7 Input Data

Write

Read

I/O

Module

Slot 0

I/O

Module

Slot 1

I/O

Module

Slot 7

Network READ

Network WRITE

41628