Publication 1797-6.5.3 - March 2006

2-14 Understand Configurable FLEX Ex Analog Module Features

Bit/Word Description for the Analog Input Module
(1797-IE8H)

Table 2.8 Fault Mode - Write Words 0 and 1

Table 2.9 Add-on Filter Selections - Write Words 0 and 1

Table 2.10 Remote Transmitter Error Up/Down - Write Words 0 and 1

Table 2.7 Configuration Map (Write Words)

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

Write

0

Reserved

High and Low Error Level 0…3

U/D

0…3

Filter Cutoff 0…3

Data Format 0…3

Flt

Md

0…3

1

Sqrt

High and Low Error Level 4…7

U/D

4…7

Filter Cutoff 4…7

Data Format 4…7

Flt

Md

4…7

Where:

U/D = up/down
Flt Md = Fault Module
Sqrt = Square Root

Word 0

Bit 00

Fault enable for channels 0…3

Word 1

Bit 00

Fault enable for channels 4…7

Where:

0 = disabled
1 = enable with wire-off and overload or short circuit

Word

Bits

Description

0

07 06 05 Channels 0…3

1

07 06 05 Channels 4…7

0

0

0

Reserved

0

0

1

0

1

0

0

1

1

10 Hz (100 ms)

1

0

0

4 Hz (250 ms)

1

0

1

2 Hz (500 ms)

1

1

0

1 Hz (1 s)

1

1

1

0.5 Hz (2 s)

Word 0

Bit 08

Up/down channels 0…3

Word 1

Bit 08

Up/down channels 4…7

Where:

0 = remote fault is enabled by transmitter overrange
1 = remote fault is enabled by transmitter underrange

Advertising