How to Install Your FLEX Ex Analog Modules 3-5

Mount on a DIN Rail

1. Remove the cover plug in the male connector of the unit to which you

are connecting this terminal base unit.

2. Check to make sure that the 16 pins in the male connector on the

adjacent device are straight and in line so that the mating female
connector on this terminal base unit will mate correctly.

3. Make certain that the female flexbus connector is fully retracted into

the base unit.

4. Position the terminal base over the 35 x 7.5mm DIN rail A

(A-B pt. no. 199-DR1).

ATTENTION

Do not remove or replace a terminal base unit when power is
applied. Interruption of the flexbus can result in unintended
operation or machine motion.

A

A

41106

Position terminal base at a slight angle and
hooked over the top of the DIN rail A.