Publication 1797-6.5.3 - March 2006

Specifications A-11

1797-OE8H CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0 to ch 7 (terminals: 0 to 1; 4 to 5; 8 to 9; 12 to 13;
17 to 18; 21 to 22; 25 to 26; 29 to 30)

Keyswitch Position

4

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock, Operating
Shock, Non-Operating
Vibration

-20…+70 °C (-4…158 °F)
-40…+85 °C (-40…185 °F)
5…95% noncondensing
Tested to 15 g peak acceleration, 11 (+1)ms pulse width
Tested to 15 g peak acceleration, 11 (+1)ms pulse width
Tested 2 g @ 10…500 Hz per IEC 68-2-6

Agency Certification

CENELEC

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)

Certificates

CENELEC

DMT 00 ATEX E 042 X

Protection

Group

Allowed
Capacitance

Allowed
Inductance

Internal
Capacitance

Internal
Inductance

U

o

= 21.6V

I

o

= 92 mA

P

o

= 500 mW

EEx ia

IIB

1.18

µF

1.18

µF

10 nF

0 mH

IIC

164 nF

164 nF

10 nF

0 mH