Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 93

Advertising
background image

Publication 1797-6.5.3 - March 2006

Calibrate Your Module 5-17

Table 5.12 1797-OE8H Interpretation of Calibration Data Structure Content During Read Access (Error Status)

Command Byte

Item Byte

Data1 Byte

Data2 Byte

Status (Binary)

Command Bits 0…5 (Decimal)

01

Error

3

The written min scale value of Current was not
accepted/internal read back erroneous

Channel-Mask

Value
low-byte

Value
high-byte

4

The written min scale value of Voltage was not
accepted/internal read back erroneous

5

The written max scale value of Current was not
accepted/internal read back erroneous

6

The written max scale value of Voltage was not
accepted/internal read back erroneous

7

Reserved

(1)

Reserved

(1)

Reserved

(1)

Reserved

(1)

8

The calibration values are not set to default

0

0

0

9

The specified calibration value is not set to default Value-identifier

10

The specified calibration value is not written

Value
low-byte

Value
high-byte

11

Reserved

(2)

Reserved

(2)

Reserved

(2)

Reserved

(2)

12

Reserved

(2)

13

Reserved

(2)

14

Reserved

(2)

15…61 Unknown command is mirrored back

0

0

0

62

The specified setup value is not written

(3)

Setup
value-identifier

Value
low-byte

Value
high-byte

63

The setup data could not be saved to EEPROM

(3)

0

0

0

(1)

Do not use. Designated for future use.

(2)

Reserved. Used during manufacture of the product. Do not use.

(3)

Only for internal use. Do not use for calibration purposes.