Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 153

Advertising
background image

Publication 1797-6.5.3 - March 2006

Additional HART Protocol Information C-5

Response Code

This two-byte code contains the HART field device status as sent by that
device. Field devices detecting a communications error set the most significant
bit, bit 7, of the first byte and identify the error in the other seven bits. If the
last message was received without error, the field device will clear bit 7 and
return a device-dependent response in the other seven bits.

The second byte of this response code returns the operating status of HART
field devices. This byte may default to 0 when a communications error occurs
as indicated by bit 7 of the first byte being set.

IMPORTANT

The host controller ignores any values in the data
field when a communications error is detected.

Table C.3 HART Protocol — Communication Error Code

Bit

Error Code

Description

7

Communications error

If set, the field device has detected a
communications error. Bits 0…6 indicate the
type of error.

6

Vertical parity error

The parity of one or more of the bytes received
by the HART field device is incorrect.

5

Overrun error

At least one byte of data in the receive buffer of
the HART field device was over-written before it
was read.

4

Framing error

The stop bit of one or more bytes received by the
HART field device was not detected.

3

Longitudinal parity error

The longitudinal parity calculated by the HART
field device does not match the longitudinal
parity byte at the end of the packet.

2

Reserved

Set to 0.

1

Buffer overflow

The packet is too long for the receive buffer of
the HART field device.

0

Undefined

Not defined.

Advertising
This manual is related to the following products: