Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 115

Advertising
background image

Publication 1797-6.5.3 - March 2006

Specifications A-3

1797-IE8H CE, CENELEC I/O Entity Parameters

Measurement input (sig to -) for ch 0 to 7 (terminals: 1 to 2; 5 to 6; 9 to 10; 13
to 14; 18 to 19; 22 to 23; 26 to 27; 30 to 31)

Source output (+ to sig) for ch 0 to 7 (terminals: 0 to 1; 4 to 5; 8 to 9; 12 to 13;
17 to 18; 21 to 22; 25 to 26; 29 to 30)

Source output plus measurement input (+ to -) for ch 0 to 7 (terminals: 0 to 2;
4 to 6; 8 to 10; 12 to 14; 17 to 19; 21 to 23; 25 to 27; 29 to 31)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 5V

I

o

= 1 mA

P

o

= 1.3 mW

EEx ia

IIB

1000 µF

1 H

U

i

= 28V

I

i

= 93 mA

C

i

and L

i

negligible

IIC

100 µF

1 H

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 23.7V

I

o

= 92.5 mA

P

o

= 548 mW

EEx ia

IIB

560 nF

10 mH

IIC

66 nF

2.5 mH

If concentrated
capacitance
and/or
inductance are
available, use the
following values.

EEx ia

IIB

320 nF

10 mH

IIC

60 nF

2 mH

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 23.7V

I

o

= 93.5 mA

P

o

= 555 mW

EEx ia

IIB

560 nF

10 mH

IIC

66 nF

2.5 mH

If concentrated
capacitance
and/or
inductance are
available, use the
following values.

EEx ia

IIB

320 nF

10 mH

IIC

60 nF

2 mH

Advertising
This manual is related to the following products: