Publication 1797-6.5.3 - March 2006

5-2 Calibrate Your Module

When and How to Calibrate
Your FLEX Ex Analog I/O
Module

Your module is shipped already calibrated. If a calibration check is
required, the module must be in a FLEX Ex I/O system.

Perform module calibration periodically, based on your application. Module
calibration may also be required to remove module error due to aging of
components in your system.

Use one of these general methods to calibrate your module:

• Intrinsically safe equipment

• Factory trained personnel under controlled conditions with

non-intrinsically safe equipment to maintain your module’s intrinsic
safety certification

Tools and Equipment

Use the following tools and equipment to calibrate your analog I/O modules:

ATTENTION

Your FLEX Ex analog I/O modules are intrinsically safe
equipment. This module cannot be used in instrinsically safe
environment after having been exposed to non-intrinsically safe
signals.

ATTENTION

Calibration personnel must use extreme care to avoid
compromising the intrinsically safe characteristics of the
modules. This method may never be used in a hazardous
environment.

Table 5.1 Tools for Calibration

Tool or Equipment

Description

Precision Current Source

0…22 mA, 0.01 µA
resolution

Used for input modules

Precision Current Meter

0…22 mA, 0.01 µA
resolution

Used for output modules

Industrial Terminal and
Interconnect Cable

Programming terminal for A-B family controllers