Inputs/outputs – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 63

Advertising
background image

Publication 1797-6.5.3 - March 2006

How to Install Your FLEX Ex Analog Modules 3-11

Connecting Wiring to the
FLEX Ex I/O Analog
Modules

Inputs/Outputs

Each 1797-IE8H input can be operated from an analog field device signal, and
each 1797-OE8H output channel can operate an analog field device. Do not
apply any non-intrinsically safe signals to these modules
.

The channels of the 1797-IE8H are electrically connected to each other and
have a common plus-line. The channels of the 1797-OE8H are electrically
connected to each other.

Connections for the 1797-IE8H Module

IMPORTANT

When using an intrinsically safe electrical apparatus according
to EN50020, the European Community directives and
regulations must be followed.

IMPORTANT

When interconnecting several lines, you must consider the total
accumulated power and check for intrinsic safety.

1

0

2

3

4

5

6

7

8

9

10

11

12

13

14

15

28

29

30

31

32

33

22

23

24

25

26

27

16

17

18

19

20

21

46

47

48

49

50

51

40

41

42

43

44

45

34

35

36

37

38

39

40071

Ch 0

Ch 1

Ch 2

Ch 3

Ch 4

Ch 5

Ch 6

Ch 7

Row C

Row A

Row B

+ sig –

+ sig –

+ sig –

+ sig –

+ sig –

+ sig –

+ sig –

+ sig –

No connection
allowed

No connection
allowed

+V

+V

–V

–V

flexbus

Bus

uC

+V

-V

+

sig

-

4 to 20mA

Xmit

4 to 20mA

Xmit

I

P

P

I

40072

22

91

17V

1797-IE8H Module

Advertising