Publication 1797-6.5.3 - March 2006

Calibrate Your Module 5-5

1797-IE8H Calibration Command Byte

The Calibration command byte uses the following format to write to the
module:

The Calibration command byte uses the following format to read from the
module:

Table 5.3 1797-IE8H Calibration Command List

Calibration Command (Decimal)
Bits 0…5

Function

0

Reserved

1

Calibrate offset at 25 °C

2

Calibrate gain at 25 °C

3…7

Reserved

8

Set all calibration values to default

9

Set one specified calibration value to
default

10…13

Reserved

(1)

(1)

Used during manufacture of the product. Do not use.

14

Save calibration content to EEPROM

15…63

Reserved

7

6

5

4

3

2

1

0

Calibration command

Reserved (10

bin

must be written)

7

6

5

4

3

2

1

0

Last Calibration command mirrored back

Status of last written Calibration command
00

bin

= last written command executed/idle

01

bin

= error occurred during execution of last

command, command aborted

10

bin

= last written command pending

11

bin

= reserved