Understand Configurable FLEX Ex Analog Module Features 2-17

Table 2.15 Configuration Map (Write Words)

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

0

Lo Flt

Md

Rese

rved

Flt

Md

ch

2…3

Flt

Md

ch

0…1

Alg Flt

Ste

ch

2…3

Alg Flt

Ste

ch

0…1

Data Format

ch 2…3

Data Format

ch 0…1

1

Lth
Md

ch

4…7

Lth
Md

ch

0…3

Flt

Md

ch

6…7

Flt

Md

ch

4…5

Alg Flt

Ste

ch

6…7

Alg Flt

Ste

ch

4…5

Data Format

ch 6…7

Data Format

ch 4…5

2

Dig

Flt

Ste

ch 7

Dig

Flt

Ste

ch 6

Dig

Flt

Ste

ch 5

Dig

Flt

Ste

ch 4

Dig

Flt

Ste

ch 3

Dig

Flt

Ste

ch 2

Dig

Flt

Ste

ch 1

Dig

Flt

Ste

ch 0

Alg
Dig
Md

ch 7

Alg
Dig
Md

ch 6

Alg
Dig
Md

ch 5

Alg
Dig
Md

ch 4

Alg
Dig
Md

ch 3

Alg
Dig
Md

ch 2

Alg
Dig
Md

ch 1

Alg
Dig
Md

ch 0

3

Analog Fault State Value Channel 0

4

Analog Fault State Value Channel 1

5

Analog Fault State Value Channel 2

6

Analog Fault State Value Channel 3

7

Analog Fault State Value Channel 4

8

Analog Fault State Value Channel 5

9

Analog Fault State Value Channel 6

10

Analog Fault State Value Channel 7

Where:

ch = channel
Lo Flt Md = Local Fault Mode
Flt Md = Fault Mode
Alg Flt Ste = Analog Fault State
Lth Md = Latch Mode
Dig Flt Ste = Digital Fault State
Alg Dig Md = Analog/Digital Mode
Cd Flg = Command Flag