Command 143, Command 144 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 141

Advertising
background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-17

Command 143

The Reset Count of Host Communications command resets the
communication statistic. There are no request or response data bytes.

Command 144

The Read Retry Limits command retries in case of busy with 0 to 11 (default is
0). It also retries in case of communication errors with 0 to 11 (default is 2).
There are no request data bytes.

Command-specific Response Codes

5

Error

Too few data bytes received

16

Error

Access restricted

17

Error

Too many items requested

32

Error Busy

Table B.17 Command 143 Command-specific Response Codes

Command-specific Response Codes

16

Error

Access restricted

32

Error

Busy

Table B.18 Command 144 Response Data Bytes

Byte

Description

Value

0

BUSY_RETRY

Number of retries for a busy response from
instrument

0…11

1

OTHER_RETRY

Number of retries for another error
instrument

0…11

Command-specific Response Codes

16

Error

Access restricted

32

Error

Busy

Table B.16 Command 141 Request and Response Data Bytes

Byte

Description

Value

Advertising