Connect and apply power to the devicenet network, Connect and apply power to the, Devicenet network – Rockwell Automation 1769-L23E-QB1B_L23E-QBFC1B_L23-QBFC1B CompactLogix Packaged Controllers Quick Start and User Manual User Manual
Page 129: 1606-xl

Publication IASIMP-QS010B-EN-P - October 2009
129
Optional - Configuration of the DeviceNet Network Chapter 7
Connect and Apply Power to the DeviceNet Network
1606-XLDNET8 power supply
Input
AC 100
-120/200-240V
N L
Isolate po
wer bef
ore disc
onnec
ting
1606-XL
POWER SUPPL
Y
DC ok
Output
200W Limi
ted Powe
r
DC 24V / 8A
+ –
DC ok
AC 120V
AC 240V
1. Connect incoming power to the
power supply.
2. Place the switch in the position that
matches your supply voltage.
3. Connect the DeviceNet power tap
to the power supply.
For this example, there is no need to connect the DC ok relay on the power supply to
anything.
4. If you have unused DeviceNet wires, make sure they do not come into contact with
the other wires.
5. Connect the DeviceNet power tap to the DeviceNet network.
6. Turn on incoming power.
WARNING
Verify that all incoming
power is turned off before
wiring power.
Connect
To
V AC COM
N (neutral)
120/240V AC
L (line)
Ground
Connect
To
Red
+
White
N/A
Shield
N/A
Blue
N/A
Black
–