Use this table as a reference when determining how to configure your
Ethernet network RPI.

We recommend that you leave some connections available for tasks, such as
going online and non-I/O purposes.

Maximum Ethernet Interface Connections

The maximum connection specifications for the Ethernet interface of the
1769-L23E controllers are listed in this table.

Ethernet Interface Connections According to RPI

Requested
Packet Interval

Ethernet Interface
Connections, max

2 ms

2

4 ms

5

8 ms

10

16 ms

18

32 ms+

25+

Connection Type

Number of
Connections, max

TCP

8

CIP, Class 1 (I/O and Produce/Consume)

32

CIP, Class 3 (Messaging)

32