Chapter 6 Battery Maintenance

Estimate 1769-BA
Battery Life

Certain conditions affect typical battery life. Use this table to estimate your
battery life in varying conditions.

Battery Life Estimation

After the BATT indicator first indicates a low battery, use this table to
determine the amount of time you have until the battery can no longer support
memory in the event of a power loss.

Store Batteries

Additional Resources

For more information, consult Guidelines for Handling Lithium Batteries,
publication

AG 5.4

, which comes with your replacement battery.

Controller Power

At 25 °C (77 °F)

At 40 °C (104 °F)

At 60 °C (140 °F)

Always Off

14 months

12 months

9 months

On 8 hours per day, 5 days per
week

18 months

15 months

12 months

On 16 hours per day, 5 days per
week

26 months

22 months

16 months

Always On

There is almost no drain on the battery when the controller is always on.

If the temperature is approx.

Then change the battery within

60 °C (140 °F)

8 days

25 °C (77 °F)

25 days

ATTENTION

Follow these general rules to store your batteries:

Store batteries in a cool, dry environment. We recommend 25 °C
(77 °F) with 40…60% relative humidity.

You may store batteries for up to 30 days between -45…85 °C
(-49...185 °F), such as during transportation.

To avoid leakage or other hazards, do not store batteries above
60 °C (140 °F) for more than 30 days.